The technical team frequently receives inquiries about the extent to which a switchboard upgrade should be carried out.

When conducting a domestic switchboard upgrade, we would recommend as a minimum the following:

  • All final sub circuits in domestic are RCD protected. 
  • Commercial switchboards Light and Power up to and including 32a circuits RCD protected.
  • Not more than three circuit breakers on one RCD (domestic).
  • Conduct an insulation resistance test A-E & N-E on all final subcircuits before reconnection.
  • Check the MEN and if metal enclosure check the box bond size and serviceability.
  • Check main earth ( <0.5Ω ) size as per AS/NZS 3000 table 5.1. 
  • Main Earth conductor and earth stake serviceability, exposed to the weather and accessible, connection painted & tagged.
  • Check for any equipotential bonding.
  • Ensure there is a cable route diagram ( if known ) location of main earth and circuit labeling.
  • General visual inspection of the switchboard.

For any questions contact the technical team on 08 6241 6100

Sponsors

ECA WA / ETI Balcatta Head Office & Member Services Christmas and NYE Closure Details

Please be advised that the Electrotechnology Training Institute Ltd (ETI) and all associated business units will be closed for the 2025-26 Christmas and New Year period from Friday 19 December 2025 – Sunday 4 January 2026. All locations and services will re-open on Monday 5 January 2026.

We wish you and your loved ones a safe and happy festive season and look forward to continuing to support you and your business in the New Year.

For urgent matters or queries during this time, please contact  Aidan O'Grady - 0408 545 699

Technical Hotline extended hours

The Technical Hotline will be taking direct calls to their 1300 hotline number during the closure period as follows: